UPS output power rating (0,9 p.f.) |
|
kVA |
8 |
10 |
12 |
15 |
20 |
30 |
|
kW |
7.2 |
9 |
10.8 |
13.5 |
18 |
27 |
|
General |
|
Efficiency in double conversion mode (full load) |
92% (without transformer) |
93% (without transformer) |
|
Efficiency in double conversion mode (half load) |
90% (without transformer) |
91% (without transformer) |
|
Distributed paralleling with Hot Sync technology |
4 |
|
Field upgradeable |
yes |
|
Inverter/rectifier topology |
transformer-free IGBT with PWM |
|
Audible noise |
< 50 dB |
|
Colour |
RAL 7035 |
|
Input |
|
Nominal voltage rating (configurable) |
380, 400, 415 V 50/60 Hz |
|
With transformer |
e.g. 230, 400, 440, 480, 690 V (internal) |
e.g. 230, 440, 480, 690 V (external) |
|
Input voltage range |
Low -20% at 100% load/-50% at 50% load without battery discharge; High +10%/max +20% |
|
Input frequency range |
45-65 Hz |
|
Input power factor |
0,99 |
|
Input ITHD |
less than 4,5% |
|
Soft start capability |
Yes |
|
Internal backfeed protection |
Yes |
|
Output |
|
Nominal voltage rating (configurable) |
380, 400, 415V 50/60 Hz |
220, 230, 240V 50/60 Hz |
|
With external transformer |
e.g. 230, 400, 440, 480, 690 V |
e.g. 230, 440, 480, 690 V |
|
Output UTHD |
<3% (100% linear load); <5% (reference non linear load) |
|
Output power factor |
0,9 (e.g. 9 kW at 10 kVA) |
0,9 (e.g. 27 kW at 30 kVA) |
|
Permitted load power factor |
0,7 lagging - 0,8 leading |
|
Battery |
|
Type |
Maintenance-free VRLA batteries, NiCd |
|
Charging method |
ABM technology or Float |
|
Temperature compensation |
Optional |
|
Battery nominal voltage (lead-acid) |
384 V (32x12 V, 192 cells) |
432 V (36x12 V, 216 cells) |
|
Charging current / Model |
Default 3 A
*Max 30 A |
Default 3 A
*Max 60 A |
|
*May be limited by maximum UPS input current rating |
|
Accessories |
|
|
Isolation transformer, long-life batteries, external battery cabinets, UPS Center (input, bypass, distribution), X-Slot connectivity (Web/SNMP, ModBus/ Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external maintenance bypass switch |
Isolation transformer, long-life batteries, external battery cabinets, X-Slot connectivity (Web/SNMP, ModBus/ Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external maintenance bypass switch |
|
Communications |
|
X-Slot |
2 communication bays |
|
Serial ports |
1 available |
|
Relay inputs/outputs |
2/1 programmable |
|
Compliance with standards |
|
Safety (CB certified) |
IEC 62040-1, IEC 60950-1 |
|
EMC |
IEC 62040-2, IEC 60945 |
|
Performance |
IEC 62040-3 |
|
Approvals |
CE, DNV Type Approval, BV Type Approval and ABS PDA up to 15kVA |
|
Other classification survey reports |
On request |